Accessories

High quality accessories complete the range of Pneumatex pressure maintenance products. Thus technology becomes system technology. These products are suitable for application in systems specified to EN 12828 and SWKI 93-1.

Product Information

for pressure maintenance

High quality accessories complete the range of Pneumatex pressure maintenance products. Thus technology becomes system technology. These products are suitable for application in systems specified to EN 12828 and SWKI 93-1.

Technical description – Intermediate vessels

Applications:

Heating, solar and chilled water systems.

Functions:

Protection against inadmissible temperature in expansion vessels.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: see Articles

Temperature:

Intermediate vessel DD/DU:
Max. admissible temperature, TS: 110 °C
Min. admissible temperature, TSmin: -10 °C
Intermediate vessel DG:
Max. admissible temperature, TS: 180 °C
Min. admissible temperature, TSmin: -10 °C

Material:

Steel. Color beryllium.

Transportation and storing:

In frostless, dry places.

Approvals:

CE design-tested according to PED/DEP 97/23/EC.

Technical description – Blow tank

Applications:

Heating water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Installation behind safety valves for the separation of steam/water mixtures.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Dimensioning for a flow counter pressure of max. 2 bar

Temperature:

Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C

Material:

Steel. Color beryllium.

Transportation and storing:

In frostless, dry places.

Approvals:

Constructed according to SWKI 93-1, amendment 1.

Technical description – Low water protection

Applications:

Heating water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Protection of the heat generator and the system from overheating in case of lack of water.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 10 bar

Temperature:

Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C

Material:

Main body made of nodular graphite iron, zinc coated.

Transportation and storing:

In frostless, dry places.

Approvals:

Component inspected TÜV-HWB-96.

Technical description – Safety valves

Applications:

Heating water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Protection of the maximum pressure on heat generators.

Pressure:

DSV...H:
Max. admissible pressure, PS: 10 bar
Min. admissible pressure, PSmin: 0 bar
DSV...DGH (DN 25-32):
Max. admissible pressure, PS: 25 bar
Min. admissible pressure, PSmin: 0 bar
DSV...DGH (DN 40-50):
Max. admissible pressure, PS: 16 bar
Min. admissible pressure, PSmin: 0 bar

Accurancy:

DSV...H:
Closing pressure tolerance: 0,5 bar
Open pressure tolerance: 0,5 bar
DSV...DGH:
Closing pressure tolerance: PSV* 0,1 bar
Open pressure tolerance: PSV* 0,1 bar

Temperature:

Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C

Media:

DSV...H: Addition of antifreeze agent up to 30%.
DSV...DGH: Addition of antifreeze agent up to 50%.

Material:

DSV...H, DSV...DGH (DN 25-32): Gun metal.
DSV...DGH (DN 40-50): Nodular graphite iron GGG: Colour beryllium.

Approvals:

DSV...H:
CE-component inspected according to TRD 721-TÜV SV xx-516 H, PED/DEP 97/23/EC-01 202 111-B-00027.
DSV...DGH (DN 25-32):
CE-component inspected according to TRD 721-TÜV SV xx-665 DGH, PED/DEP 97/23/EC-01 202 111-B-00029.
DSV...DGH (DN 40-50):
CE-component inspected according to TRD 721-TÜV SV xx-2007 DGH, PED/DEP 97/23/EC-01202 111-B-06079.

Warranty:

DSV...DGH: Secuguard version, 5-year warranty.

Technical description – Pre-pressure measuring gauge

Applications:

Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Control of the pre-pressure at expansion vessels. Auto on/off. Automatic calibration.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 10 bar

Temperature:

Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C

Material:

Rugged plastic housing.

Technical description – Manometer

Applications:

Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Control of the filling pressure at expansion vessels.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 4 bar

Temperature:

Max. admissible temperature, TS: 60 °C
Min. admissible temperature, TSmin: -10 °C

Technical description – Thermometer/Manometer

Applications:

Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Control of the filling pressure at expansion vessels.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 4 bar

Temperature:

Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C

Technical description – Push button valve

Applications:

Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Shut-off of manometers. Pressure measurement only with pressed piston, otherwise the manometer is unpressurized.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 30 bar

Temperature:

Max. admissible temperature, TS: 100 °C
Min. admissible temperature, TSmin: -20 °C

Material:

Nickle-plated brass.

Technical description – Lock shield valve

Applications:

Heating, solar and cooling water systems.
Deployment in systems according to EN 12828, SWKI 93-1.

Functions:

Shut-off. Maintenance and disassembly of expansion vessels.

Pressure:

Min. admissible pressure, PSmin: 0 bar
Max. admissible pressure, PS: 16 bar

Temperature:

Max. admissible temperature, TS: 120 °C
Min. admissible temperature, TSmin: -10 °C

Media:

Non-aggressive and non-toxic system media.
Addition of antifreeze agent up to 50%.

Material:

Brass.

General:

Can only be closed with an allen key which is include in the supply, ball valve with DN 15 hose connection for fast draining.

Product Articles

Intermediate vessels - Articles

Intermediate vessel DD

Wall bracket for the easy assembly.

Type
VN
[l]
D
H**

[kg]
S
EAN
Article No
10 bar (PS)
DD 8.10
8
345
166
3,9
2x R1/2
7640148634359
714 2020
DD 12.10
12
386
201
5,1
2x R1/2
7640148634366
714 2021
DD 18.10
18
430
224
6,3
2x R3/4
7640148634373
714 2022
DD 25.10
25
472
251
8,1
2x R3/4
7640148634380
714 2023
DD 35.10
35
521
280
10
2x R3/4
7640148634397
714 2024
DD 50.10
50
587
317
12,2
2x R1
7640148634403
714 2025
DD 80.10
80
687
347
16,4
2x R1
7640148634410
714 2026

**) Tolerance 0 /+35

Intermediate vessel DU

Sinus ring for upright assembly.

Type*
VN
[l]
D
H

[kg]
S
EAN
Article No
6 bar (PS)
DU 140.6
140
420
1316
25
2x Rp1 1/2
7640148634427
714 1002
DU 200.6
200
500
1384
30
2x Rp1 1/2
7640148634434
714 1003
DU 300.6
300
560
1517
35
2x Rp1 1/2
7640148634441
714 1004
DU 400.6
400
620
1580
55
2x Rp1 1/2
7640148634458
714 1005
DU 500.6
500
680
1673
61
2x Rp1 1/2
7640148634465
714 1006
DU 600.6
600
740
1678
67
2x Rp1 1/2
7640148634472
714 1007
10 bar (PS)
DU 200.10
200
500
1384
50
2x Rp1 1/2
7640148634489
714 2003
DU 300.10
300
560
1517
55
2x Rp1 1/2
7640148634496
714 2004
DU 500.10
500
680
1673
83
2x Rp1 1/2
7640148634502
714 2006

*) Vessels > 500 litres, 10 bar upon request.

Intermediate vessel DG

Feet for upright assembly.
Two flange openings for internal inspections.

Type
VN
[l]
D
H**

[kg]
S
EN 1092-1
EAN
Article No
6 bar (PS)
DG 700.6
700
750
2087
200
2xDN50
7640148634519
714 1008
DG 1000.6
1000
850
2210
280
2xDN50
7640148634526
714 1009
DG 1500.6
1500
1016
2391
385
2xDN50
7640148634533
714 1010
DG 2000.6
2000
1016
2909
655
2xDN65
7640148634540
714 1015
DG 3000.6
3000
1300
3008
810
2xDN65
7640148634557
714 1012
DG 4000.6
4000
1300
3653
920
2xDN65
7640148634564
714 1013
DG 5000.6
5000
1300
4300
1015
2xDN65
7640148634571
714 1014
10 bar (PS)
DG 300.10
300
500
1965
170
2xDN50
7640148634588
714 2008
DG 500.10
500
650
2014
225
2xDN50
7640148634595
714 2009
DG 700.10
700
750
2087
240
2xDN50
7640148634601
714 2010
DG 1000.10
1000
850
2211
330
2xDN50
7640148634618
714 2011
DG 1500.10
1500
1016
2394
445
2xDN50
7640148634625
714 2012
DG 2000.10
2000
1016
2918
735
2xDN65
7640148634632
714 2017
DG 300010
3000
1300
3024
890
2xDN65
7640148634649
714 2014
DG 4000.10
4000
1300
3669
1030
2xDN65
7640148634656
714 2015
DG 5000.10
5000
1300
4314
1145
2xDN65
7640148634663
714 2016
16 bar (PS)
DG 300.16
300
500
1965
190
2xDN50
7640148634670
714 3000
DG 500.16
500
650
2016
255
2xDN50
7640148634687
714 3001
DG 700.16
700
750
2087
280
2xDN50
7640148634694
714 3002
DG 1000.16
1000
850
2247
385
2xDN50
7640148634700
714 3003
DG 1500.16
1500
1016
2393
510
2xDN50
7640148634717
714 3004
DG 2000.16
2000
1016
2935
820
2xDN65
7640148634724
714 3012
DG 3000.16
3000
1300
3040
995
2xDN65
7640148634731
714 3006
DG 4000.16
4000
1300
3685
1145
2xDN65
7640148634748
714 3007
DG 5000.16
5000
1300
4330
1280
2xDN65
7640148634755
714 3008

**) Tolerance 0 /-100.

Blow tank

Blow tank ET

Connections for safety valve, steam line and drain line.
Vertical installation.

Type
D
H

[kg]
SE
SA
SW
EAN
Article No
2 bar (PS)
ET 32-125
133
312
4,5
DN 32
DN 65
DN 15
7640148634762
785 2500
ET 65-250
285
500
9
DN 65
DN 125
DN 20
7640148634779
785 2501
ET 100-400
405
760
23,5
DN 100
DN 200
DN 25
7640148634786
785 2502
ET 150-600
605
1022
38
DN 150
DN 300
DN 32
7640148634793
785 2503

DSV – ET allocation

DSV...H
ET
DSV...DGH
PSV ≤ 5 bar
ET
PSV > 5 bar
ET
DSV 15H
*
-
-
-
DSV 20H
*
-
-
-
DSV 25H
*
DSV 25DGH
ET 65-250
ET 65-250
DSV 32H
ET 65-250
DSV 32DGH
ET 65-250
ET 65-250
DSV 40H
ET 100-400
DSV 40DGH
ET 65-250
ET 100-400
DSV 50H
ET 100-400
DSV 50DGH
ET 100-400
ET 100-400

*) No ET as QPSV < 350 kW.

Low water protection

Low water protection WMS

Locking after turning off, change-over contact for signalling.
2 welding connections.
Vertical installation.

Type
H
L

[kg]
U
[V]
I
[A]
EAN
Article No
10 bar (PS)
WMS 933.1
370
195
3,3
250
10
7640148638630
502 1003

Low water protection WMS

No locking after turning off, change-over contact for signalling.
2 welding connections.
Vertical installation.

Type
H
L

[kg]
U
[V]
I
[A]
EAN
Article No
10 bar (PS)
WMS 933.2
370
195
3,3
250
10
7640148638647
502 1004

Safety valves

Safety valve DSV...H

Spring-loaded, can be vented manually, spring compartment protected by diaphragms.
Inlet and outlet side with internal thread, outlet side increased.
Vertical installation.

Type
PSV
[bar]
QPSV
[kW]
QPSVW
[kW]
H
L
Kg
SE
SA
EAN
Article No
DSV 15-2.5 H
2,5
73
73
98
52
0,3
G1/2
G3/4
7640148634809
537 1025
DSV 15-3.0 H
3,0
81
81
98
52
0,3
G1/2
G3/4
7640148634816
537 1030
DSV 20-2.5 H
2,5
135
135
99
62
0,45
G3/4
G1
7640148634823
537 2025
DSV 20-3.0 H
3,0
151
151
99
62
0,45
G3/4
G1
537 2030
DSV 25-2.5 H
2,5
229
229
116
70
0,75
G1
G1 1/4
7640148634847
537 3025
DSV 25-3.0 H
3,0
254
254
116
70
0,75
G1
G1 1/4
7640148634854
537 3030
DSV 32-2.5 H
2,5
446
446
132
87
1,1
G1 1/4
G1 1/2
7640148634861
537 4025
DSV 32-3.0 H
3,0
496
496
132
87
1,1
G1 1/4
G1 1/2
537 4030
DSV 40-2.5 H
2,5
672
672
209
98
2,2
G1 1/2
G2
7640148634885
537 5025
DSV 40-3.0 H
3,0
747
747
209
98
2,2
G1 1/2
G2
7640148634892
537 5030
DSV 50-2.5 H
2,5
1025
1025
250
118
3,2
G2
G2 1/2
7640148634908
537 6025
DSV 50-3.0 H
3,0
1040
1140
250
118
3,2
G2
G2 1/2
7640148634915
537 6030

Safety valve DSV...DGH

Spring loaded, with manual blow off lever, spring chamber is bellow sealed, pressure balanced.
Inlet and outlet side with internal thread, outlet side increased.
Vertical installation.

Type*
PSV
[bar]
QPSV
[kW]
QPSVW
[kW]
H
L
Kg
SE
SA
EAN
Article No
DSV 25-2.0 DGH
2,0
192
16940
233
86
1,8
G1
G1 1/2
7640148635028
536 3020
DSV 25-2.5 DGH
2,5
222
18940
233
86
1,8
G1
G1 1/2
7640148635073
536 3025
DSV 25-3.0 DGH
3,0
320
20750
233
86
1,8
G1
G1 1/2
7640148635127
536 3030
DSV 25-3.5 DGH
3,5
357
22410
233
86
1,8
G1
G1 1/2
7640148635172
536 3035
DSV 25-4.0 DGH
4,0
393
23960
233
86
1,8
G1
G1 1/2
7640148635226
536 3040
DSV 25-4.5 DGH
4,5
430
25410
233
86
1,8
G1
G1 1/2
7640148635271
536 3045
DSV 25-5.0 DGH
5,0
465
26790
233
86
1,8
G1
G1 1/2
7640148635325
536 3050
DSV 32-2.0 DGH
2,0
333
28830
316
110
4,0
G1 1/4
G2
7640148635936
536 4020
DSV 32-2.5 DGH
2,5
385
32230
316
110
4,0
G1 1/4
G2
7640148635981
536 4025
DSV 32-3.0 DGH
3,0
555
35300
316
110
4,0
G1 1/4
G2
7640148636032
536 4030
DSV 32-3.5 DGH
3,5
619
38130
316
110
4,0
G1 1/4
G2
7640148636087
536 4035
DSV 32-4.0 DGH
4,0
682
40770
316
110
4,0
G1 1/4
G2
7640148636131
536 4040
DSV 32-4.5 DGH
4,5
746
43240
316
110
4,0
G1 1/4
G2
7640148636186
536 4045
DSV 32-5.0 DGH
5,0
808
45580
316
110
4,0
G1 1/4
G2
7640148636230
536 4050

*) Further DSV...DGH valves can be supplied from 1,0 to 10 bar in steps of 0,1 bar.

Safety valve DSV...DGH

Spring loaded, with manual blow off lever, spring chamber is bellow sealed.
Inlet and outlet with flanged connections and increased outlet size.
Vertical installation.

Type*
PSV
[bar]
QPSV
[kW]
QPSVW
[kW]
H
L
Kg
SE
SA
EAN
Article No
DSV 40-2.0 DGH
2,0
780
44658
485
190
17
DN 40
DN 65
7640148636841
536 5020
DSV 40-2.5 DGH
2,5
920
49929
485
190
17
DN 40
DN 65
7640148636896
536 5025
DSV 40-3.0 DGH
3,0
1040
54695
485
190
17
DN 40
DN 65
7640148636940
536 5030
DSV 40-3.5 DGH
3,5
1160
59077
485
190
17
DN 40
DN 65
7640148636995
536 5035
DSV 40-4.0 DGH
4,0
1280
63156
485
190
17
DN 40
DN 65
7640148637046
536 5040
DSV 40-4.5 DGH
4,5
1400
66987
485
190
17
DN 40
DN 65
7640148637091
536 5045
DSV 40-5.0 DGH
5,0
1510
70611
485
190
17
DN 40
DN 65
7640148637145
536 5050
DSV 50-2.0 DGH
2,0
1190
69031
495
203
19
DN 50
DN 80
7640148637756
536 6020
DSV 50-2.5 DGH
2,5
1400
77179
495
203
19
DN 50
DN 80
7640148637800
536 6025
DSV 50-3.0 DGH
3,0
1600
84545
495
203
19
DN 50
DN 80
7640148637855
536 6030
DSV 50-3.5 DGH
3,5
1790
91319
495
203
19
DN 50
DN 80
7640148637909
536 6035
DSV 50-4.0 DGH
4,0
1980
97624
495
203
19
DN 50
DN 80
7640148637954
536 6040
DSV 50-4.5 DGH
4,5
2160
103546
495
203
19
DN 50
DN 80
7640148638005
536 6045
DSV 50-5.0 DGH
5,0
2330
109147
495
203
19
DN 50
DN 80
7640148638050
536 6050

*) Further DSV...DGH valves can be supplied from 1,0 to 10 bar in steps of 0,1 bar.

Blow off capacity

QPSV: Related to steam flow for direct fired heat generator (e.g. gas, oil, electric, ...).QPSVW: Related to water flow for indirect fired heat generator (e.g. water to water heat exchanger) in case the temperature of the primary circuit tpr does not enable a possible vaporisation of the secondary system water. The values given in the table must not be exceeded (wet vapour pressure pD(tpr) ≤ PSV).

PSV [bar]
2,0
2,5
3,0
3,5
4,0
4,5
5,0
tpr [oC]
133,5
138,5
143,5
148,0
152,0
156,0
160,0

Pre-pressure measuring gauge

Pre-pressure measuring gauge DME

Type
PS
[bar]

[kg]
EAN
Article No
DME
10
0,3
7640148638593
500 1048

Manometer

Manometer H

Display range 0-4 bar, with 3 adjustable plastic segments for the marking of the desired green pressure bandwith.
Bottom connection.

Type
PS
D

[kg]
S
EAN
Article No
H4
4
80
0,3
R1/2
7640148638616
501 1037

Thermometer/Manometer

Thermometer/Manometer TH

Pressure display range 0-4 bar, temperature display range 0-120 °C, with 3 adjustable plastic segments for the marking of the desired green pressure bandwith.
Rear connection.

Type
PS
[bar]
D

[kg]
S
EAN
Article No
TH4
4
80
0,3
R1/2
7640148638623
501 1038

Push button valve

Push button valve DH

Type
PS
[bar]

[kg]
S
EAN
Article No
DH
30
0,3
G1/2
7640148638609
500 1060

Lock shield valve

Lock shield valve DLV

Female thread on both sides, screw connection on the vessel connection side.

Type
PS
[bar]
L

[kg]
S
SG
SW
EAN
Article No
DLV 15
16
117
0,7
Rp3/4
Rp1/2
G3/4
7640148638562
535 1432

Lock shield valve DLV

Female thread on both sides, flat sealing union for direct connection to all suitable expansion vessels.

Type
PS
[bar]
L

[kg]
S
SG
SW
EAN
Article No
DLV 20
16
92
0,6
Rp3/4
G3/4
G3/4
7640148638579
535 1434
DLV 25
16
95
0,7
Rp1
G1
G3/4
7640148638586
535 1436

Connection set DLV A

Female thread on both sides, 90° bend with threaded seal for direct connection to Statico SU expansion vessels.

Type
PS
[bar]
L

[kg]
S
SG
SW
EAN
Article No
DLV 20 A
16
128
0,8
Rp3/4
Rp3/4
G3/4
7640148639842
746 2000

Animations & Films

Use our interactive animations to simulate the effects of our innovative product as it would perform in your HVAC system. See our product films and learn more about how our products can help you. Click the play button to get started!

Photos

Download all

Drawings

Download all

2D/3D

Download all

Technical Specifications