Our website uses cookies to better meet your requirements. Proper configuration of browser options allows you to block or remove cookies but can also cause the site to not function properly or even at all. By continuing to use the site, with no change to your browser settings, you agree to the use of cookies.
Learn about our Privacy Policy for cookies and other similar technologies.

RTL

Among other things, the return temperature limiter RTL is used to limit the return temperatures of radiators or combined floor/radiator systems to equalize the temperature of smaller floor surfaces (up to ca. 15 m2).

Product Information

Return temperature limiter

Among other things, the return temperature limiter RTL is used to limit the return temperatures of radiators or combined floor/radiator systems to equalize the temperature of smaller floor surfaces (up to ca. 15 m2).

Technical description

The return temperature limiter RTL is an automatic thermostatic controller. The temperature of the flowing medium is transferred to the sensor via conductivity. This keeps the specified value constant within a proportional band necessary for control. The valve only opens when the set limiting value has not been reached.
Sensor element with concealed upper and lower temperature range limiting or blocking of the settings using stop clips. Thermostat filled with an expansible medium. Overstroke safety. White cover with printed scale.
Valve body made of nickel-plated gunmetal (angle/straight). With stainless spindle and double O-ring seal. Outer O-ring can be replaced without draining the system.
Potential connections using the model with inside threading for threaded pipe or with compression fittings for copper, precision steel, or multi-layer pipe. For the model with outside thread, potential connection with additional compression fittings for plastic pipe.
For the RTL return temperature limiter use only the accompanying, labeled IMI Heimeier compression fittings (e.g. 15 THE).
Attention: The RTL return temperature limiter is constructed from a special valve body and sensor element. Thermostatic valve bodies cannot be used.

The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.imi-hydronic.com.

Product Articles

Animations & Films

Use our interactive animations to simulate the effects of our innovative product as it would perform in your HVAC system. See our product films and learn more about how our products can help you. Click the play button to get started!

Text for Tenders