Our website uses cookies to better meet your requirements. Proper configuration of browser options allows you to block or remove cookies but can also cause the site to not function properly or even at all. By continuing to use the site, with no change to your browser settings, you agree to the use of cookies.
Learn about our Privacy Policy for cookies and other similar technologies.

MDFO

Flow measuring orifice with self-sealed measuring points.

Product Information

Flow measuring orifice

Flow measuring orifice with self-sealed measuring points.

Technical description

Application:

Heating and cooling systems
Tapwater systems

Function:

Measuring

Dimensions:

DN 20-900

Pressure class:

PN 16 (DN 20-900)
PN 25 (DN 65-300)
PN 40 (DN 65-450)

Temperature:

Max. working temperature: 120°C
Min. working temperature: -20°C

Material:

Fixed orifice: Stainless steel X3CrNiMo17-13-3 (No. 1.4436 according to EN 10028-7 or EN 10272 (BS 970 316/S16)
Measuring points: AMETAL®
Sealing (measuring points): EPDM


AMETAL® is the dezincification resistant alloy of IMI Hydronic Engineering.

Marking:

TA, MDFO, DN, PN, Charge No, flow direction arrow.