DA 516, DAF 516

These compact differential pressure controllers for heating and cooling systems are particularly effective in situations requiring high temperatures and/or pressure drop. They can be used both on the primary and secondary side in district heating and comfort cooling systems. Rust protection is assured thanks to the electrophoretically painted ductile iron body.

Product Information

Differential pressure controller with adjustable set-point

These compact differential pressure controllers for heating and cooling systems are particularly effective in situations requiring high temperatures and/or pressure drop. They can be used both on the primary and secondary side in district heating and comfort cooling systems. Rust protection is assured thanks to the electrophoretically painted ductile iron body.

Technical description

Application:

Heating and cooling systems with variable flow.

Functions:

Differential pressure control over the load.

Dimensions:

DN 15-150

Pressure class:

PN 25
DN 100-150: PN 16 and PN 25

Max. differential pressure (ΔpV):

1600 kPa = 16 bar

Setting range:

Δp over the load is adjustable within:
DN 15-125: 5-30 kPa, 10-60 kPa, 10-100 kPa or 60-150 kPa.
DN 150: 5-30 kPa, 10-60 kPa, 10-100 kPa, 60-150 kPa or 100-400 kPa.
Delivery setting:
DN 15-50: Maximum value (30, 60, 100 resp. 150 kPa).
DN 65-125: Midway min./max. value (~18, ~35, ~55, resp. ~105 kPa).
DN 150: Minimum value (5, 10, 10, 60 resp. 100 kPa).

Temperature:

Max. working temperature: 120°C
Min. working temperature: -10°C

Media:

Water and neutral fluids, water-glycol mixtures.

Material:

Valve body: Ductile iron EN-GJS-400
Diaphragms and gaskets: EPDM
Adjustment ring: DN 15-50 Ryton PPS, DN 65-125 R St 37-2 steel. (DN 150 has no adjustment ring)

Surface treatment:

Electrophoretic painting.

Marking:

TA, DN, PN, Material, Kvs, Δp and flow direction arrow.

Flanges:

DN 15-50: According to EN-1092-2:1997, type 16.
DN 65-150: According to EN-1092-2:1997, type 21.

Product Articles

DA 516

With measuring point

Capillary pipe (Ø6) included: 1 200 mm

PN 25

DN
d
L
L1*
H2
Kvs
Kg
EAN
5-30 kPa
15/20
G1
106
116
79
4
1,5
25/32
G1 1/4
125
150
84
12
2,6
40/50
G2
162
190
102
30
5,8
10-60 kPa
15/20
G1
106
116
79
4
1,5
25/32
G1 1/4
125
150
84
12
2,6
40/50
G2
162
190
102
30
5,8
10-100 kPa
15/20
G1
106
116
79
4
1,5
25/32
G1 1/4
125
150
84
12
2,6
3831112507135
40/50
G2
162
190
102
30
5,8
3831112507173
60-150 kPa
15/20
G1
106
116
79
4
1,5
25/32
G1 1/4
125
150
84
12
2,6
3831112507166
40/50
G2
162
190
102
30
5,8
3831112507203

*) Length incl adjustment ring.

With measuring point

Capillary pipe (Ø6) included: 1 500 mm

PN 25 (DN 65-80 also fit PN 16 flanges)

DN
D
L
Kvs
EAN
5-30 kPa
65
210
160
60
80
210
160
60
100
320
254
150
125
320
254
150
10-60 kPa
65
210
160
60
80
210
160
60
100
320
254
150
125
320
254
150
10-100 kPa
65
210
160
60
3831112507265
80
210
160
60
3831112507302
100
320
254
150
3831112507388
125
320
254
150
3831112507463
60-150 kPa
65
210
160
60
3831112507296
80
210
160
60
3831112507333
100
320
254
150
3831112507418
125
320
254
150
3831112507494

PN 16

DN
D
L
Kvs
EAN
5-30 kPa
100
320
254
150
125
320
254
150
10-60 kPa
100
320
254
150
125
320
254
150
10-100 kPa
100
320
254
150
125
320
254
150
60-150 kPa
100
320
254
150
125
320
254
150

With measuring points

Capillary pipe (Ø6) included: 1 500 mm

PN 25

DN
D
L
Kvs
EAN
5-30 kPa
150
382
267
280
10-60 kPa
150
382
267
280
10-100 kPa
150
382
267
280
60-150 kPa
150
382
267
280
100-400 kPa
150
382
267
280

PN 16

DN
D
L
Kvs
Kg
EAN
150
382
267
280
85
150
382
267
280
85
150
382
267
280
85
150
382
267
280
85
150
382
267
280
85

→ = Flow direction

DAF 516

Without measuring point

Capillary pipes (Ø6) included: 2 x 1 200 mm

PN 25

DN
d
L
L1*
H1
Kvs
Kg
Article No
5-30 kPa
15/20
G1
106
116
41
4
1,5
52 763-120
25/32
G1 1/4
125
150
51
12
2,6
52 763-125
40/50
G2
162
190
70
30
5,8
52 763-140
10-60 kPa
15/20
G1
106
116
41
4
1,5
52 761-120
25/32
G1 1/4
125
150
51
12
2,6
52 761-125
40/50
G2
162
190
70
30
5,8
52 761-140
10-100 kPa
15/20
G1
106
116
41
4
1,5
52 760-120
25/32
G1 1/4
125
150
51
12
2,6
52 760-125
40/50
G2
162
190
70
30
5,8
52 760-140
60-150 kPa
15/20
G1
106
116
41
4
1,5
52 762-120
25/32
G1 1/4
125
150
51
12
2,6
52 762-125
40/50
G2
162
190
70
30
5,8
52 762-140

*) Length incl adjustment ring.

Without measuring point

Capillary pipes (Ø6) included: 2 x 1 500 mm

PN 25 (DN 65-80 also fit PN 16 flanges)

DN
D
L
Kvs
5-30 kPa
65
210
160
60
80
210
160
60
100
320
254
150
125
320
254
150
10-60 kPa
65
210
160
60
80
210
160
60
100
320
254
150
125
320
254
150
10-100 kPa
65
210
160
60
80
210
160
60
100
320
254
150
125
320
254
150
60-150 kPa
65
210
160
60
80
210
160
60
100
320
254
150
125
320
254
150

PN 16

DN
D
L
Kvs
5-30 kPa
100
320
254
150
125
320
254
150
10-60 kPa
100
320
254
150
125
320
254
150
10-100 kPa
100
320
254
150
125
320
254
150
60-150 kPa
100
320
254
150
125
320
254
150

→ = Flow direction

Connections for DN 15-50

With female thread

Threads according to ISO 228

d1
d2
L1*
EAN
Article No
G1
G1/2
26
3831112501027
52 759-015
G1
G3/4
32
3831112501034
52 759-020
G1 1/4
G1
47
3831112501041
52 759-025
G1 1/4
G1 1/4
52
3831112501058
52 759-032
G2
G1 1/2
52
3831112503489
52 759-040
G2
G2
64,5
3831112503205
52 759-050

With female thread Rc

Threads according to ISO 7-1

d1
d2
L1*
EAN
Article No
G1
Rc1/2
26
3831112527454
52 751-301
G1
Rc3/4
32
3831112527461
52 751-302
G1 1/4
Rc1
47
3831112527478
52 751-303
G1 1/4
Rc1 1/4
52
3831112527485
52 751-304
G2
Rc1 1/2
52
3831112527492
52 751-305
G2
Rc2
64,5
3831112527508
52 751-306

With male thread

Threads according to ISO 7

d1
d2
L1*
EAN
Article No
G1
R1/2
34
3831112500983
52 759-115
G1
R3/4
40
3831112500990
52 759-120
G1 1/4
R1
40
3831112501003
52 759-125
G1 1/4
R1 1/4
45
3831112501010
52 759-132
G2
R1 1/2
45
3831112503342
52 759-140
G2
R2
50
3831112503472
52 759-150

For welding

d1
D
L1*
EAN
Article No
G1
20,8
37
3831112500945
52 759-315
G1
26,3
42
3831112500952
52 759-320
G1 1/4
33,2
47
3831112500969
52 759-325
G1 1/4
40,9
47
3831112500976
52 759-332
G2
48,0
47
3831112501140
52 759-340
G2
60,0
52
3831112501294
52 759-350

With flange

Attention! Can be used on the inlet side only.

d1
d2
D
L1*
EAN
Article No
G1
M12
95
10
3831112501065
52 759-515
G1
M12
105
20
3831112501072
52 759-520
G1 1/4
M12
115
5
3831112504318
52 759-525
G1 1/4
M16
140
15
3831112501096
52 759-532
G2
M16
150
5
3831112504325
52 759-540
G2
M16
165
20
3831112501317
52 759-550

With flange (extended)

Attention! Must be used on the outlet side.

d1
d2
D
L1*
EAN
Article No
G1
M12
95
47
3831112501157
52 759-615
G1
M12
105
47
3831112500136
52 759-620
G1 1/4
M12
115
62
3831112503533
52 759-625
G1 1/4
M16
140
62
3831112526129
52 759-632
G2
M16
150
72
3831112505025
52 759-640
G2
M16
165
72
3831112503892
52 759-650

*) Fitting length (from the gasket surface to the end of the connection).

Accessories

Connection set STAD

Must be used on STAD when connection of 6 mm capillary pipe.

d
EAN
Article No
G1/2
7318793850003
52 762-006
G3/4
7318793850102
52 762-106

Measuring point, two-way

For connection of 6 mm copper pipe while permitting simultaneous use of TA Hydronics measuring or balancing instruments.

EAN
Article No
7318793848703
52 179-206

Animations & Films

Use our interactive animations to simulate the effects of our innovative product as it would perform in your HVAC system. See our product films and learn more about how our products can help you. Click the play button to get started!

Photos

Download all

Drawings

Download all

2D/3D

Download all

Technical Specifications

Installation Instructions