STAP – DN 65-100

The flanged STAP is a high-performing differential pressure controller that keeps the differential pressure over the load constant. This delivers accurate and stable modulating control, ensures less risk of noise from control valves, and results in easy balancing and commissioning. STAP’s unrivalled accuracy and compact size make it particularly suitable for use on the secondary side of heating and cooling systems.

Product Information

Differential pressure controller

The flanged STAP is a high-performing differential pressure controller that keeps the differential pressure over the load constant. This delivers accurate and stable modulating control, ensures less risk of noise from control valves, and results in easy balancing and commissioning. STAP’s unrivalled accuracy and compact size make it particularly suitable for use on the secondary side of heating and cooling systems.

Technical description

Application:

Heating and cooling systems.

Functions:

Differential pressure control
Adjustable Δp
Measuring points
Shut-off

Dimensions:

DN 65-100

Pressure class:

PN 16

Max. differential pressure (ΔpV):

350 kPa

Setting range:

20-80 kPa resp 40-160 kPa.

Temperature:

Max. working temperature: 120°C
Min. working temperature: -10°C

Materials:

Valve body: Cast iron EN-GJL-250 (GG 25)
Bonnet: AMETAL®
Cone: AMETAL®
Spindles: AMETAL®
O-rings: EPDM rubber
Seat seal: Plug with EPDM O-ring
Membrane: Reinforced EPDM rubber
Spring: Stainless steel
Handwheel: Polyamide

AMETAL® is the dezincification resistant alloy of TA.

Surface treatment:

Valve body: Epoxy painting.

Marking:

Body: TA, PN 16, DN, CE, 250 CI, flow arrow and casting date (year, month, day).
Bonnet and handwheel: Label with STAP, DN, ΔpL 20-80 resp 40-160 kPa and bar code.

Face to face dimensions:

ISO 5752 series 1, BS 2080

Flanges:

ISO 7005-2.

Product Articles

Articles

STAP DN 65-100

PN 16, ISO 7005-2

DN
Number of
bolt holes
D
L
H
Kvm
Kg
EAN
Article No
20-80 kPa
65
4
185
290
321
36
26
7318793750402
52 265-065
80
8
200
310
337
55
32
7318793750600
52 265-080
100
8
220
350
350
110
35
7318793750808
52 265-090
40-160 kPa
65
4
185
290
321
36
26
7318793750501
52 265-165
80
8
200
310
337
55
32
7318793750709
52 265-180
100
8
220
350
350
110
35
7318793750907
52 265-190

1 m capillary pipe and transition nipple with shut-off are included.

→ = Flow direction

Kvm = m3/h at a pressure drop of 1 bar and opening corresponding to the p-band (-25%).

Accessories

Measuring point STAP

EAN
Article No
7318793660602
52 265-205

Measuring point, two-way

For connection of capillary pipe while permitting simultaneous use of TA's balancing instrument.

EAN
Article No
7318793784100
52 179-200

Capillary pipe connection with shut-off

EAN
Article No
7318793781604
52 265-206

Capillary pipe

L
EAN
Article No
1 m
7318793661500
52 265-301

Extension kit for capillary pipe

Complete with connections for 6 mm pipe

EAN
Article No
7318793781505
52 265-212

Setting tool ΔpL

L
H
EAN
Article No
207
72
5 mm
7318793975409
52 265-304

Plug

Venting

EAN
Article No
7318793661609
52 265-302

Animations & Films

Use our interactive animations to simulate the effects of our innovative product as it would perform in your HVAC system. See our product films and learn more about how our products can help you. Click the play button to get started!

Photos

Download all

Drawings

Download all

2D/3D

Download all

Technical Specifications

Installation Instructions

Legal Documents