Our website uses cookies to better meet your requirements. Proper configuration of browser options allows you to block or remove cookies but can also cause the site to not function properly or even at all. By continuing to use the site, with no change to your browser settings, you agree to the use of cookies.
Learn about our Privacy Policy for cookies and other similar technologies.

Multibox

Multibox is used for decentralized control of floor or wall heating systems or combined floor/radiator heating systems. For out-of-true installation offsetting up to 6° on each side. Cover with concealed screw connection. Models in white or chrome. Adjustable fitting for all wall structures, 30 mm depth compensation.

Product Information

Flush individual room control for floor heating systems

Multibox is used for decentralized control of floor or wall heating systems or combined floor/radiator heating systems. For out-of-true installation offsetting up to 6° on each side. Cover with concealed screw connection. Models in white or chrome. Adjustable fitting for all wall structures, 30 mm depth compensation.

Multibox K, RTL and K-RTL

Technical description

Applications:

Floor heating systems, wall heating systems, combined floor/radiator heating systems

Functions:

Multibox K:
Individual room temperature control,
Presetting (V-exact II),
Shut-off,
Venting
Multibox RTL:
Maximum limitation of the return temperature,
Presetting,
Shut-off,
Venting
Multibox K-RTL:
Individual room temperature control,
Maximum limitation of the return temperature,
Presetting (V-exact II),
Shut-off,
Venting

Dimensions:

Valve body DN 15.
The flush box has an overall depth of 60 mm.
Flexible mounting thanks to variable spacing between flush box and cover of up to 30 mm.
The cover can compensate for slanted mounting of the flush box of up to 6° on each side.
See also Dimensions.

Pressure class:

PN 10

Setting range:

Thermostatic head K:
6 °C to 28 °C
Return temperature limiter RTL:
0 °C to 50 °C

Temperature:

Max. working temperature: 90°C
Min. working temperature: 2°C
For all Multibox models, ensure that the system supply temperature is suitable for setting up the floor heating system.
See also Information!

Material:

Valve body: Corrosion resistant Gunmetal
O-rings: EPDM rubber
Valve disc: EPDM rubber
Return spring: Stainless steel
Valve insert: Brass, PPS (polyphenylsulphide)
Spindle: Niro-steel spindle with double O-ring sealing. The outer O-ring can be replaced under pressure.
Plastic parts of ABS and PA.
Sensor element: Thermostatic head K with liquid filled sensor. Return temperature limiter (RTL) filled with an expansible medium.

Surface treatment:

All models optionally with cover and visible graduation cap in white RAL 9016 or chrome-plated.

Marking:

TAH, flow direction arrows, II-Designation.

Pipe connection:

Pipe-side G 3/4 adaptor with cone suitable for compression fittings for plastic, copper, precision steel and multi-layer pipe.

Multibox F

Technical description

Applications:

Floor heating systems, wall heating systems

Functions:

Individual room temperature control
Presetting
Shut-off
Venting

Dimensions:

Valve body DN 15.
The flush box has an overall depth of 60 mm.
Flexible mounting thanks to variable spacing between flush box and cover of up to 30 mm.

Through a capillary tube, the temperature sensor liquid of the thermostatic head acts on the bellows in the valve adaptor. There is therefore never any change in the appearance of the cover with thermostatic head – irrespective of the installation depth.
The cover can compensate for slanted mounting of the flush box of up to 6° on each side.
See also Dimensions.

Pressure class:

PN 10

Setting range:

Thermostatic head F:
6 °C to 28 °C

Temperature:

Max. working temperature: 90 °C
Min. working temperature: 2 °C
For all Multibox models, ensure that the system supply temperature is suitable for setting up the floor heating system.
See also Information!

Material:

Valve body: Corrosion resistant Gunmetal
O-rings: EPDM rubber
Valve disc: EPDM rubber
Return spring: Stainless steel
Valve insert: Brass, PPS (polyphenylsulphide)
Spindle: Niro-steel spindle with double O-ring sealing. The outer O-ring can be replaced under pressure.
Plastic parts of ABS and PA.
Sensor element: Thermostatic head F with liquid filled sensor.

Surface treatment:

Cover and visible graduation cap in white RAL 9016.

Marking:

TAH, flow direction arrow, II-Designation.

Pipe connection:

Pipe-side G 3/4 adaptor with cone suitable for compression fittings for plastic, copper, precision steel and multi-layer pipe.

Multibox C/E and C/RTL

Technical description

Applications:

Floor heating systems, wall heating systems, combined floor/radiator heating systems

Functions:

Multibox C/E:
Individual room temperature control with thermal or motorized actuators or with remote dial thermostatic head F,
Presetting,
Shut-off,
Venting
Multibox C/RTL:
Maximum limitation of the return temperature,
Presetting,
Shut-off,
Venting

Dimensions:

Valve body DN 15.
The flush box has an overall depth of 60 mm.
Flexible mounting thanks to variable spacing between flush box and cover of up to 30 mm.
The cover can compensate for slanted mounting of the flush box of up to 6° on each side.
See also Dimensions.

Pressure class:

PN 10

Setting range:

Return temperature limiter RTL:
0 °C to 50 °C

Temperature:

Max. working temperature: 90 °C
Min. working temperature: 2 °C
For all Multibox models, ensure that the system supply temperature is suitable for setting up the floor heating system.
See also Information!

Material:

Valve body: Corrosion resistant Gunmetal
O-rings: EPDM rubber
Valve disc: EPDM rubber
Return spring: Stainless steel
Valve insert: Brass, PPS (polyphenylsulphide)
Spindle: Niro-steel spindle with double O-ring sealing. The outer O-ring can be replaced under pressure.
Plastic parts of ABS and PA.
Sensor element: Return temperature limiter (RTL) filled with an expansible medium.

Surface treatment:

Cover in white RAL 9016.

Marking:

TAH, flow direction arrows, II-Designation.

Pipe connection:

Pipe-side G 3/4 adaptor with cone suitable for compression fittings for plastic, copper, precision steel and multi-layer pipe.

The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by TA Hydronics without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.tahydronics.com.